similar products

750kW Chiller

Specification Calculators
Nominal Cooling Duty750 kW
Design Duty746 kW
Inlet Temperature+12°C
Outlet Temperature+7°C
Ambient+35°C
Compressor Power263.5 kW
EER2.8
Noise Levels64.1 dBA @ 10 Metres
ControlAutomatic Programmer
Power Consumption263.57 kW/h
Water Connections6” Bauer Male & Female
Buffer Vessel500 Litres
Water PumpNSCE 80-160/185/P25VCCZ
Compressors8
Compressor TypeScroll
Capacity Steps8
Refrigerant TypeR410a
No. of Circuits4
Noise Level64.1 dBA @ 10m
Evaporator TypePlate
Number of Circuits4
Design Flow128.3 m³/h
Pressure Drop54 kPa
Max System Pressure4 bar
Fan Quantity8
Fan TypeAxial
Electrical Power415vAC 3Ø, N + Eth
Full Load Amps589.6 Amps
Start Amps929 A
Unit ConnectionHardwired
Dry Weight7,500 Kg
Dimensions (WxLxH)2,384 x 6,527 x 2,555 mm

© 2006 - 2017 All Season Hire Ltd. All rights reserved. Web design by Planet